Permit Number: T07CM03771
Parcel: 12216115A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM03771
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
09/18/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the size of the condensate drain piping per Section 307.2.2, IMC 2006, as amended by the City of Tucson.
09/18/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM03771 9/18/07

1. Keynotes 5 and 31 on Sheet E-1 both indicate New Panel R1. Please clarify.
2. Circuit R-15, R-17, and R-19 power EV3, EV4, and EV5 on Power Plan, but power EV4, Space, and Space on panel schedule. Please clarify.
3. CU-4 is powered by R-19,20,22 on Power Plan, and R-14,16,18 on panel schedule. Please clarify.
4. Indicate circuiting for Two-Head Steamer on Power Plan.
5. On Panel Schedule, fill in load information for R-3, R-5, R-7, R-9, and R-11.
6. 125% demand factor shall be added to metered load. Reference NEC 220.87.
7. Show location of New Panel R on Sheet E-1. (Electrical Plans Examiner to check fault calculations after this has been done.)
09/18/2007 ROBERT SHERRY WATER REVIEW Approved
09/18/2007 JWILLIA5 BUILDING-COMMERCIAL REVIEW Approved 1) Provide 20% ADA Budget Calculations.
2) Provide 1 more Exit. Occupancy Load > 50.
Per Roger Brooks
09/18/2007 JASON GREEN ENGINEERING REVIEW Approved
09/18/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the backflow protection for the directly connected appliances with sheet A-3 and Section 603.0, UPC 2006, as amended by the City of Tucson. The appliances shall be individually protected.
09/18/2007 DAVE MANN FIRE REVIEW Approved
09/18/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/25/2007 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2007 DELMA ROBEY APPROVAL SHELF Completed
09/25/2007 DELMA ROBEY OUT TO CUSTOMER Completed
09/25/2007 DELMA ROBEY REJECT SHELF Completed