Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM03771
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/18/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
09/18/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the size of the condensate drain piping per Section 307.2.2, IMC 2006, as amended by the City of Tucson. |
09/18/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM03771 9/18/07 1. Keynotes 5 and 31 on Sheet E-1 both indicate New Panel R1. Please clarify. 2. Circuit R-15, R-17, and R-19 power EV3, EV4, and EV5 on Power Plan, but power EV4, Space, and Space on panel schedule. Please clarify. 3. CU-4 is powered by R-19,20,22 on Power Plan, and R-14,16,18 on panel schedule. Please clarify. 4. Indicate circuiting for Two-Head Steamer on Power Plan. 5. On Panel Schedule, fill in load information for R-3, R-5, R-7, R-9, and R-11. 6. 125% demand factor shall be added to metered load. Reference NEC 220.87. 7. Show location of New Panel R on Sheet E-1. (Electrical Plans Examiner to check fault calculations after this has been done.) |
09/18/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/18/2007 | JWILLIA5 | BUILDING-COMMERCIAL | REVIEW | Approved | 1) Provide 20% ADA Budget Calculations. 2) Provide 1 more Exit. Occupancy Load > 50. Per Roger Brooks |
09/18/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
09/18/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Coordinate the backflow protection for the directly connected appliances with sheet A-3 and Section 603.0, UPC 2006, as amended by the City of Tucson. The appliances shall be individually protected. |
09/18/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
09/18/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/25/2007 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/25/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
09/25/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
09/25/2007 | DELMA ROBEY | REJECT SHELF | Completed |