Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM03741
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/19/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. On 1st Generation Revision, the electrical loads of Panel PP1 Phase B abruptly changed without revision cloud. This is mysterious because Phases A and C are similar in nature and did not change. If the original 22920 VA on PP1 is carried through in tabulating electrical loads, then Panel PP4 will be overloaded. 2. On 1st Generation Revision, the GND on the secondaries of the transformers, properly sized per NEC Table 250.66, would be 1/0, not #3. However, coordinate this comment with those pertaining to the 2nd Generation Revision, below. 3. On 2nd Generation Revision, the GND on the secondaries of the transformers, properly sized per NEC Table 250.66, would be 1/0, not #2. 4. On 1st and 2nd Generation Revisions, Revision #4 on Sheet E6 is dated 1/28/08, but they are different revisions. Clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/19/2008 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |