Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review T07CM03741 6/13/08

1. The GND on the secondary to the transformer feeding PP5 is properly sized at 1/0, not #2. NEC Table 250.66.
2. Add Revision 5 to Title Block, with date.

INCOMPLETE REVIEW. ASSEMBLE 2 SETS OF REVISED SHEETS AND PRESENT FULL SIZED SET OF PREVIOUSLY APPROVED DRAWINGS.