Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM03741
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T07CM03741 6/13/08 1. The GND on the secondary to the transformer feeding PP5 is properly sized at 1/0, not #2. NEC Table 250.66. 2. Add Revision 5 to Title Block, with date. INCOMPLETE REVIEW. ASSEMBLE 2 SETS OF REVISED SHEETS AND PRESENT FULL SIZED SET OF PREVIOUSLY APPROVED DRAWINGS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/17/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |