Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM03741
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2007 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 12/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/20/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/21/2007 | MATT FLICK | ENGINEERING | REVIEW | Approved | |
| 12/28/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Plumbing plans shall demonstrate that Water Heaters are cord-connected. THIS COMMENT WAS MADE ON THE REVIEWS OF 10/2/07 AND 12/5/07. Written response on printout of comments states that these Water Heaters are NOT cord-connected. Please provide a disconnecting means per NEC 422 Part III. 2. Distances for F2, F3, and F4 still scale out to be 5', 8' and 11' respectively, not 25', 40', and 55'. So available fault currents at Panels PP2, PP3, and PP5 come out to be 23,436A, 23,215A, and 22,999A respectively, not 22050, 21092, and 20232. THIS COMMENT WAS MADE ON THE REVIEWS OF 10/2/07 AND 12/5/07. 3. Please note that the series ratings of 42K/22K on Sheet E6 do not coordinate with the 25K ratings on the panel schedules. If these panels are fully rated for 25K there is no need to specify series ratings for any system components. THIS COMMENT WAS MADE ON THE REVIEW OF 12/05/07. |