Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM03503
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/24/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM03503 8/24/07 1. Water heater shall be considered as a continuous load. Reference NEC 422.13. 2. Please provide conductor size for 30A Ckt 23-25. 3. New water heater draws 45A at 5400VA per phase. Please re-evaluate the 40A circuit. |
| 08/24/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that there is adequate maintenance access for the new water heater. 2. Revise the location of the vent for the 3-compartment sink to comply with Section 1014.2.1, UPC 2006. 3. Provide material standards for all plumbing fixtures being provided by others. Reference Section 401.1, UPC 2006. |