Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Approved
08/24/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM03503 8/24/07

1. Water heater shall be considered as a continuous load. Reference NEC 422.13.
2. Please provide conductor size for 30A Ckt 23-25.
3. New water heater draws 45A at 5400VA per phase. Please re-evaluate the 40A circuit.
08/24/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that there is adequate maintenance access for the new water heater.
2. Revise the location of the vent for the 3-compartment sink to comply with Section 1014.2.1, UPC 2006.
3. Provide material standards for all plumbing fixtures being provided by others. Reference Section 401.1, UPC 2006.