Permit Number: T07CM03308
Parcel: 141113700

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM03308
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2008 MARTIN BROWN FIRE REVIEW Approved
02/22/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: February 21, 2008
SUBJECT: Metal Building
TO: Tom Cattany
LOCATION: 8233 S Camino De Cafe
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T07CM03308 (First Review)


RESUBMITTAL REQUIRED: Metal Building

SUMMARY: Engineering Division of Development Services Department has received and reviewed the resign request for the metal building for the above referenced property. Engineering Division does not recommend approval of the submittal at this time. Please address the following review comments prior to the next submittal.

Resign for Metal Building:

1. Building plans are to be accompanied by last approved development plan. Plan submitted for resign does not include building plans nor is the new development plan have approval stamp.

2. Please resubmit with proper documentation.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
02/26/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 2: CURB RAMP DETAILS 4: THIS DETAIL STILL DOES NOT WORK. TRUNCATED DOMES SHOULD BE RELOCATED PER ANSI 117.1/406.13 AND 705.5. LANDING LENGTH PER FIGURE 405.7. HANDRAILS PER 405.8 AND 505.
03/10/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/11/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Table 902.1, IBC 2006 requires at least one drinking fountain per 400 occupants in F-1 occupancies. In addition, the drinking fountain shall meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
2. Tucson Water locates all water meters at the road, not at the building. Revise the water pressure calculations to include the correct developed pipe length from the meter to the furthest plumbing outlet (see the site plan). Reference: Section 610.2, UPC 2006.
03/19/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. The "c" value for 500 kcmil is 26706 for non-magnetic conduit, not 25000. THIS COMMENT WAS MADE ON THE REVIEWS OF 8/10/07 AND 11/21/08. Please refer to TEP Standard SR-510, which states that for single phase commercial services 400A or less, the Available Fault Current at the line terminals of the metering equipment is limited to 22,000A as long as the utility secondary is at least 45' long. If such is the case here, it is suggested that you simply document this on the plans and remove the other references to fault currents and fault calculations.
2. Please remove the redundant GND between the meter and service disconnect.
3. Note that on one of the sets, Sheet E3.0 lacks the Registrant's seal.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
03/19/2008 SHANAE POWELL REJECT SHELF Completed