Permit Number: T07CM03205
Parcel: 12706010A

Address:
40 N SWAN RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T07CM03205
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2009 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Permit # T07CM03205 Revision (Back-check)
Project: Facade Renovation

City of Tucson Development Services
Mechanical/Plumbing Plan Review

Date: 08/14/09
Address: 40 N Swan Road
Responsible Architect: Rick L. Bright, RA 20105

Plan Reviewer: Robert W. Sherry, PE

Applicable Codes:

IMC 2006 UPC 2006
IECC 2006 IBC 2006
IFGC 2006 IFC 2006


Plumbing Comments:

1. The two 2" roof drains for serving section "C" and half of section B are undersized based on Table 11-1, UPC 2006.
2. The scupper draining roof section "A" is too narrow for the area it is draining. Reference: Section 1101.11.2, UPC 2006.
3. The overflow scupper draining roof section "C" is too narrow for the area it is draining. Reference: Section 1101.11.2, UPC 2006.
4. For section "C", the height of the bottom of the overflow scupper above the low point of the roof is unclear. If it is greater than 2" above the low point of the roof, provide structural calculations to show that the roof is capable of supporting the additional rain load Section 1611.1, IBC 2006.
5. Provide information and calculations to show that the existing combination of scuppers and roof drains for roof section "E" is adequate to handle the overflow drainage from roof section "C" and half of roof section "B". Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
6. Provide information and calculations to show that the existing roof drains for the north roof section are adequate to handle the overflow drainage from roof section "A" and half of roof section "B". Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
7. Roof section "D" appears to discharge to a small area between building sections. Show how this conforms to the requirements of Section 1803.3, IBC 2006.
08/13/2009 DROBEY1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed Permit # T07CM03205 Revision (Back-check)
Project: Facade Renovation

City of Tucson Development Services
Mechanical/Plumbing Plan Review

Date: 08/14/09
Address: 40 N Swan Road
Responsible Architect: Rick L. Bright, RA 20105

Plan Reviewer: Robert W. Sherry, PE

Applicable Codes:

IMC 2006 UPC 2006
IECC 2006 IBC 2006
IFGC 2006 IFC 2006


Plumbing Comments:

1. The two 2" roof drains for serving section "C" and half of section B are undersized based on Table 11-1, UPC 2006.
2. The scupper draining roof section "A" is too narrow for the area it is draining. Reference: Section 1101.11.2, UPC 2006.
3. The overflow scupper draining roof section "C" is too narrow for the area it is draining. Reference: Section 1101.11.2, UPC 2006.
4. For section "C", the height of the bottom of the overflow scupper above the low point of the roof is unclear. If it is greater than 2" above the low point of the roof, provide structural calculations to show that the roof is capable of supporting the additional rain load Section 1611.1, IBC 2006.
5. Provide information and calculations to show that the existing combination of scuppers and roof drains for roof section "E" is adequate to handle the overflow drainage from roof section "C" and half of roof section "B". Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
6. Provide information and calculations to show that the existing roof drains for the north roof section are adequate to handle the overflow drainage from roof section "A" and half of roof section "B". Reference: Sections 103.2.3 and 1101.11.1, UPC 2006.
7. Roof section "D" appears to discharge to a small area between building sections. Show how this conforms to the requirements of Section 1803.3, IBC 2006.
08/17/2009 SREEVES1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2009 SUE REEVES OUT TO CUSTOMER Completed