Permit Number: T07CM03205
Parcel: 12706010A

Address:
40 N SWAN RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T07CM03205
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/20/2007 DAVE MANN FIRE REVIEW Approved
08/20/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 40 N. Swan - Façade Remodel
T07CM03205
Site Plan (1st Review)

TRANSMITTAL DATE: August 20, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. D.S. 2-08.5.1.A Requires a four (4) foot minimum width for a sidewalk. This said it appears that the proposed columns reduce the width of the sidewalks to less then four (4) feet. Provide dimensions showing a clear width between the proposed columns and the existing building and/or the proposed columns which are attached to the existing building.

3. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm03205.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
08/27/2007 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
09/05/2007 SUE REEVES REJECT SHELF Completed