Review Details: COMMERCIAL TI
Permit Number - T07CM02844
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Specify how many batteries are in each series string, on the plans. 2. Regarding compliance with NEC 480.9 (A), this review will be coordinated with the Mechanical Plans Examiner. |
| 07/11/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Show the spill control and define the method of neutralization on the plans. See IFC Section 608.4. Show the ventilation meets IFC 608.5. No "M" Sheets were with the submittal. Show locations of signs and smoke detectors per IFC 608. |
| 07/19/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 07/19/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 07/19/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/19/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 07/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/19/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/19/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |