Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM02470
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/14/2007 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/14/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the calculations that formed the basis for the new outside air quantities. |
| 06/14/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/14/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/14/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE LOWER THE LOUNGE SINK TO A MAXIMUM OF 34" PER SECTION 606.3 OF ANSI 117.1-2003. 2) PLEASE SPECIFY THE HORIZONTAL PLACEMENT OF THE TOILET PAPER DISPENSER PER SECTION 604.10.7 OF ANSI 117.1-2003. 3) PLEASE SPECIFY THE VERTICAL PLACEMENT OF THE VERTICAL GRAB BAR PER SECTION 604.5.1 OF ANSI 117.1-2003. 4) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE LAVATORY IN ORDER TO VERIFY COMPLIANCE WITH THE KNEE AND TOE CLEARANCES PER SECTION 606.2 ANSI 117.1-2003. 5) PLEASE REVISE THE FONT SIZE TO A MINIMUM OF 1/8" IN ACCORDANCE WITH THE SUBMITTAL REQUIREMENTS OF THE CITY OF TUCSON. 6) PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE DRINKING FOUNTAIN IN ORDER TO VERIFY COMPLIANCE WITH SECTION 602 OF ANSI 117.1-2003. PLEASE BE AWARE THAT IF IT IS A FRONT APPROACH FIXTURE, BE SURE THAT PROTECTION REGARDING THE HORIZONTAL PROJECTION HAS BEEN PROVIDED IN ACCORDANCE WITH SECTION 1003.3.3 OF THE 2003 IBC. 7) PLEASE PROVIDE ADDITIONA INFORMATION REGARDING THE DASHED WALL LINE IN STUDIO 10 PER SECTION 106.1.1 OF THE 2003 IBC. IS IT TO BE REMOVED. 8) PLEASE PROVIDE A HARD, NON-ABSORBANT SURFACE AT THE NEW WATER CLOSETS IN ACCORDANCE WITH SECTION 1210.2 OF THE 2003 IBC. 9) PLEASE SPECIFY THE WIDTH OF THE NEW HALLWAY PER SECTION 106.1.1 OF THE 2003 IBC. 10) PLEASE SPECIFY THE ACCESS WIDTH FOR THE WOMEN'S LAVATORY PER SECTION 106.1.1 OF THE 2003 IBC. 11) PLEASE SPECIFY THE FRAMING MATERIAL TO WHICH THE WATER HEATER SUPPORT IS CONNECTED PER SECTION 106.1.1 OF THE 2003 IBC. |
| 06/14/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 06/14/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 06/14/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/25/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 06/25/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |