Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T07CM01984
Parcel: 124050590

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01984
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01884 5/15/07

1. Insta-hot Specifications call for 120V power. Electrical powers on 240V. Coordinate with Plumbing and clarify.
2. 1800 VA per phase would be too small an electrical load for an existing motor load, because this represents less than 13A. This would not meet the requirements of Article 430 for Ground Fault and Short Circuit protection. Pleas re-evaluate electrical load for AC.
3. Account for both largest motor and continuous loading for Code Loads on panel schedule.
05/16/2007 DROBEY1 WWM REVIEW Needs Review
05/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/16/2007 DAVE MANN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2007 DELMA ROBEY APPROVAL SHELF Completed
05/16/2007 DELMA ROBEY OUT TO CUSTOMER Completed
05/16/2007 DELMA ROBEY REJECT SHELF Completed