Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01984
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01884 5/15/07 1. Insta-hot Specifications call for 120V power. Electrical powers on 240V. Coordinate with Plumbing and clarify. 2. 1800 VA per phase would be too small an electrical load for an existing motor load, because this represents less than 13A. This would not meet the requirements of Article 430 for Ground Fault and Short Circuit protection. Pleas re-evaluate electrical load for AC. 3. Account for both largest motor and continuous loading for Code Loads on panel schedule. |
| 05/16/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 05/16/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/16/2007 | DAVE MANN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/16/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 05/16/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/16/2007 | DELMA ROBEY | REJECT SHELF | Completed |