Review Details: COMMERCIAL TI
Permit Number - T07CM01984
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01984 5/11/07 1. Registrant shall sign and date seal on plans. 2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 3. Distinguish new from existing from relocated equipment on the plans. 4. Clarify symbols of EF and WH. 5. Show electrical load on existing panel. |
| 05/11/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 05/15/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 05/15/2007 | ANY | ENGINEERING | REVIEW | Approved | |
| 05/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/15/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/15/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/15/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/15/2007 | VFLORES1 | FIRE | REVIEW | Needs Review |