Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM01984
Parcel: 124050590

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01984
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
05/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01984 5/11/07

1. Registrant shall sign and date seal on plans.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
3. Distinguish new from existing from relocated equipment on the plans.
4. Clarify symbols of EF and WH.
5. Show electrical load on existing panel.
05/11/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
05/15/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/15/2007 ROBERT SHERRY WATER REVIEW Approved
05/15/2007 VFLORES1 FIRE REVIEW Needs Review
05/15/2007 VFLORES1 WWM REVIEW Needs Review
05/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/15/2007 ANY ENGINEERING REVIEW Approved