Permit Number - T07CM01232
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied June 4, 2007

City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Tovar Residence Addition – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM01232
WILLDAN PROJECT NO. 13881-7045

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
SFR
Porch N/A III-B 540
60 No Smoke

Special Inspection is required for the following items:
Structural Masonry

ARCHITECTURAL COMMENTS:
Reviewed and accepted.

STRUCTURAL COMMENTS:
Reviewed and accepted.

PLUMBING COMMENTS:
Sheet 3
Show the size of waste lines, vents, and required clean-outs. Reference the City of Tucson Submittal Requirements. Comment remains: Not addressed.

The City of Tucson has adopted the 2003 Uniform Plumbing Code with local amendments. All plans must reference the 2003 UPC with local amendments in its entirety. Comment remains: Not addressed.

MECHANICAL COMMENTS:
Note on plans: “Mechanical shall comply with 2003 IRC Chapters 12-24.” Reference IRC Section M1201.2. Comment remains: Not addressed.
ELECTRICAL COMMENTS:
Indicate the location of all disconnecting means for air conditioning and heating units, air handlers, compressors, and disconnects. Reference IRC Section E4001.5 and Table E4001.5. Comment remains: Not addressed.

Indicate on the plans that a minimum of 30” X 36” clear working space will be provided in front of all panels, cabinets, and disconnects. Reference IRC Section E3305.2. Comment remains: Not addressed.

Show on the plans that the service outlet will be within 25’ of evaporative cooler equipment. Reference IRC Section E3801.11. Comment remains: Not addressed.

Submit panel schedule showing wire size, panel size. Reference IRC Section 3502.2 and City of Tucson Submittal Requirements. Comment remains: Not addressed.

Please provide cut sheets for all the exterior light fixtures shown or noted on plans. The cut sheets need to provide lumens per fixture and show if the fixture is a full cut-off, which means no light is emitted at or above the horizontal plane. Please provide calculations for all exterior lighting fixtures. Reference City of Tucson Outdoor Lighting Code. Comment remains: Not addressed.

Cross-reference exterior lighting fixtures on the plans with the cut sheets and calculations submitted. Reference City of Tucson Submittal Requirements. Comment remains: Not addressed.

ENERGY CODE COMMENTS:
Reviewed and accepted.

ACCESSIBILITY COMMENTS:
Reviewed and accepted.



Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/jk