Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM01151
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2007 | DAVE MANN | FIRE | REVIEW | Denied | Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply.(Flow data - Static, Residual, GPM) 4. The design density and the area of operation. |
| 05/07/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Please note that the electrical installation shall comply with the 2002 NEC and City of Tucson, not State of Arizona amendments. Reference Sheet MEP0.1. Now, load calculations have pulled references to the 2005 NEC, which would also be acceptable because the City of Tucson is close to adopting such Code. However, it is necessary to choose one an use it consistently throughout this project. 3. It appears that the exit sign and emergency lighting in Stair Rm 150 does not comply with NEC 700.12 (E), since such fixtures are all on Ckt L1A-6. Compliance can only be achieved under the Exception to this paragraph. Typical for all areas for which this applies. 4. If the condenser is running, the fan coil must operate, or else the condenser will shut off. So add the fan coil to load calculations. And please note that it appears that certain electrical loads in the Receptacle column are not covered under NEC Table 220.44, because they are to be counted at greater than 180 VA each. Reference NEC 220.14 (I). 5. CU-8 is on Ckt L1M-38/40 on the Power Plan. This Ckt is EUH-1 on the panel schedule. Please clarify. 6. CU-9 through CU-12 are MOCP 15 on the mechanical schedule. Circuit breakers are rated for 20A. 7. Provide a disconnecting means for the automatic door opener. Reference NEC Part IX. 8. AC-3 and AC-4 have MOCP 35. CBs protect at 40A. Please clarify and correct. AC-1 has MOCP 60. CB protects at 70A. Typical for all such cases. 9. On Sheet E1.4a, please correct "LIK-24/26" to read "LIK-22/24." 10. Lighting fixtures on Sheet E1.5a are on Panel LA. Show the panel schedule. Typical for all such cases. 11. L2A-1 powers second floor corridor lighting according to the panel schedule. This circuit powers Guest Laundry, Storage, and Electrical Room as well. Please clarify. 12. Electrical loading on Panel Schedule for AC-6 does not appear to account for the full load on this circuit. 13. All Living Rooms shall have sufficient receptacles to meet the requirements of NEC 210.52 (A). 14. Show the bathroom branch circuit on the panel schedule. Reference NEC 210.11 (C) (3). 15. Demonstrate compliance with the Tucson Lighting Code, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 16. Demonstrate compliance with the 2003 IECC. 17. For all poles greater than 20' in height, submit detail and calculations for the pole and foundation, sealed by a Registered Structural Engineer. 18. Equipment Grounding Conductors run in the 400A feeders from MSB1 shall be sized per NEC Table 250.122. Minimum #3, not #6, in each parallel conduit. 19. Address the grounding for Second Building or Structure, Panel L1P. Reference NEC 250.32 (A), (B) (1). 20. Ckts L1A-9 and L1A-11 are for cab lighting per Keynote 3 on Sheet E1.6b. But on the panel schedules these circuits are for the elevator pit. Please clarify, and meet all requirements of NEC 620.22 for the car lighting, and 620.24 for pit lighting. 21. Ckts L1A and L1B are used twice, once on Detail 1 and once on Detail 2 of Sheet E1.6b. 22. Please put the lighting and receptacle loads in Room 253 on a dedicated, separate branch circuit. Reference NEC 620.23. |
| 05/07/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide energy code compliance calculations. Reference Section 101.4, International Energy Conservation Code 2003. 2. Clarify the intended use of room 253 - electrical room (detail 2/M1.5 and 2/E1.2) or elevator equipment room (A1.2)? 3. Provide protection for the duct and air transfer penetrations of the fire-resistance-rated assemblies in rooms 251,252, and 253. Reference Section 507.53, IMC 2003. 4. Revise the ventilation calculation for AC-1 (lobby) in accordance with the Section 403.3, IMC 2003, as amended by the City of Tucson. The system ventilation efficiency (section 6.2.5.2) must be used when determining the design outside air intake. 5. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5 (installed). There is no exception for short lengths of duct. Reference Section 803.2.8, IECC 2003. 6. Provide the installed weight of the Fan coil units. Reference Section 106.3.1, IMC 2003. 7. Show how adequate access is being provided for the equipment located in the attic space. Reference Section 306.3, IMC 2003. 8. Show the sizes of all of the condensate drain pipes for AC units 7, 8, 11, and 12. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003. 9. Provide information to show that the termination of the restroom exhaust complies with the requirements of Section 401.5.2, IMC 2003. 10. Provide details to show that the construction of the clothes dryer exhaust duct located in room 251 complies with the requirements of Section 504.2, IMC 2003. 11. Show that the design of the common dryer exhaust duct complies with the manufacturer's requirements or provide calculations to show that the design will not result in the accumulation of combustible lint. Reference Sections 504.1 and 105.2, IMC 2003. 12. Provide a dryer exhaust for the second commercial dryer in room 168. Reference Section 504.7, IMC 2003. 13. Provide justification for not installing a hood over the proposed convection oven in the prep area. Reference Sections 106.3.1, 202 (light-duty cooking appliance), and 507.2, IMC 2003. |
| 05/10/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide equipment data for the commercial clotheswashers. Reference Section 103.2.3, UPC 2003. 3. Clarify the fixture callouts used on the plumbing plans as compared to the plumbing fixture matrix (P3.5): SS-1and HYD-W as compared to MS-1, MS, and FPWH. Reference Section 103.2.3, UPC 2003. 4. Coordinate the water supply to the building with the site plans. The site plans show a 3" water meter and a 3" reduced pressure backflow prevention assembly near the southwest corner of the building. Note that reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf Reference Section 103.2.3, UPC 1994. 5. Clarify the specified design of the water closet seats for WC-1 and WC-2. Reference Section 103.2.3, UPC 2003. 6. Specify the required backflow prevention assembly for the fountain. Reference Section 603.0, UPC 2003. 7. Provide information to show that the hub drains called out on sheet P1.0 comply with Sections 412.1 and 804.1, UPC 2003. Clarify how this design relates to detail 3/P3.4. 8. Show how the traps shown in detail 3/P3.4 are to be protected from siphonage and backpressure. Reference Section 1002.1, UPC 2003. 9. Show the pipe sizes for the condensate drain piping shown on sheet P2.0. Reference Section 307.2.1.1, IMC 2003, as modified by the City of Tucson 10. Show how the specified drain piping for the water heater condensate will maintain a minimum horizontal slope. Reference Section 307.1, IMC 2003. 11. Clarify how the vents and intakes for the six water heaters are to be arranged on the exterior wall of room 152 and how the arrangement complies with the manufacturer's requirements for separation of the inlets and outlets and Section 510.8, UPC 2003. 12. Provide the design basis and equipment specifications for the water softener system noted on sheet P1.2. Include the pressure drop from this system in the water pressure calculations. Reference Section 103.2.3, UPC 2003. 13. Provide a floor drain in the kitchen. Reference Sections 412.2.2 and 704.3, UPC 2003. 14. Show that the floor of the restroom slopes toward the floor drain (rooms 171 and 172). Reference Section 412.2, UPC 2003. 15. Show the location of the floor drain for room 251 on the plumbing floor plan, P1.2. Reference Section 103.2.3, UPC 2003. 16. Show that the floor drains used as indirect receptors for condensate are designed to prevent splashing (e.g. such as the floor drain shown on riser #18). Reference Section 804.1, UPC 2003. 17. Provide a water hammer absorbing device for the clotheswashing machines in room 251. Reference Section 609.10, UPC 2003. 18. Provide a water hammer absorbing device for the flush valves in rooms 171 and 172. Reference Section 609.10, UPC 2003. 19. Provide suds relief for stacks 1, 2, 3, 4, 5, 6, 8, 9, 10, 12, and 13. Reference Section 711.0, UPC 2003. 20. Show how the temperature of the hot water supply to the two public lavatories is controlled to a maximum of 110 degrees Fahrenheit. Reference Section 804.3, IECC 2003. 21. The submitted water pressure calculations and pipe-sizing chart do not support the size of water piping shown for the flush valve water closets. Show that the use of 1" runouts to the flush valves will result in a minimum flowing pressure of 25 PSI for each water closet (required by the manufacturer of the specified water closets) and a maximum water velocity of 8 FPS. Reference Sections 610.1 and A6.1, UPC 2003. 22. Clarify the design of the ventilated sleeve for the gas piping located in the patio ceiling. Show how the termination of the sleeve is in a "normally usable and accessible portion of the building." Reference Section 1211.1.6, UPC 2003. 23. Clarify the note on detail 1/P2.0, "3/4" condensate down to to (sic) vent line from riser P-7". A condensate drain may not be connected to a plumbing vent. Reference Sections 103.2.3 and 311.4, UPC 2003. |
| 05/30/2007 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package. |
| 06/05/2007 | LINHART PETERSEN POERS ASSOC. | BUILDING-COMMERCIAL | REVIEW | Denied | May 29, 2007 CITY OF TUCSON - FIRST CHECK Tucson Appl. No. T07CM01151 Bureau Veritas Job No. 01007-161001.049 Cary Fisher 13647 Montfort Dr. Dallas, TX 75240 Re: Plan Review: Towneplace Suites by Marriott- STRUCTURAL ONLY Address: 6595 S. Bay Colony Dr. Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson: Plans: Two (2) sets of building plans (118 sheets, CS through P4.2) Stamped by Michael R. Mayse, Architect. Dated 04-22-2007. Structural Calculations: One set provided. Stamped by Mark Aden Structural Engineer. Truss Calculations: Two sets provided. These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC). Our comments follow on the attached list. Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded. Sincerely, Bureau Veritas North America Randy McCoy ICC Plans Examiner RMC:sk enclosures Re: Stories: Three Occupancy: R-1/VB Fire Sprinklers: Yes Building Area (sq. ft.): 49276 A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code. B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance. C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.). STRUCTURAL COMMENTS: Code references noted in the Code Summary do not correspond with the 2003 IBC. Please Clarify. Structural Calculations refer to “Existing Member Check”. Please clarify. Sheet 13 in the Structural Calculations in not ledgible. Provide calculations for the hold-downs prescribed for the shear walls. Provide floor joist structural calculations, description and location of joists. Provide complete Structural Calculations with description of members, locations, etc. If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980. 8:00 AM to 5:00 PM Monday through Friday. |
| 06/06/2007 | GERRY KOZIOL | WWM | REVIEW | Denied | 1:TOWNEPLACE SUITES BY MARRIOTT-1001 FU @ SFR RATE FOR= $189,809.62- 134FU@ COMMERCIAL RATE FOR COMMON AREAS= $50,830.22 (INCLUDES WASTE WATER SEEEWER FEES FOR 2 GUEST CLOTHES WASHERS PER FLOOR & PLUMBING PLANS. 2: NEEDS TO BUILD ON-SITE PRIVATE SEWER- NEEDS DEQREVIEW & APPROVAL TO CONSTRUCT PRIVATE SEWER- NEEDS WWM 8TH FLOORREVIEW OF LOCATION/ METHOD OF CONNECTION TO PUBLIC SEWER. NEEDS 8TH FL APPROVAL & 5TH FL WASTEWATER MANHOLE CONSTRUCTION PERMIT- NEEDS COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDAATE |
| 06/09/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
| 06/14/2007 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/11/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/11/2007 | CINDY AGUILAR | REJECT SHELF | Completed |