Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01135
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/21/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 03/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the design for the HVAC modifications: which RTU are the return air grilles to be connected to and how will the revised air flow affect the existing air distribution system? |
| 03/21/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. provide info on discon means for heaters 2. new circuits on pnl b-1 marked as spares 3. circuits for new sink pump not on plan |
| 03/21/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/21/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 03/21/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/21/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide justification for not disposing of the sink waste by gravity. Reference Section 709.0, UPC 2003. 2. Lift stations for public use require duplex pumps along with visual and audible alarms. Reference Section 710.9, UPC 2003. 3. The 2" sanitary line for the existing service sink is too small to accomodate the discharge from the lift station (2 fixture units per 1 gpm of discharge). Reference Section 710.5, UPC 2003. 4. Provide cleanouts for the pumped discharge of the lift station. Reference Sections 707.4 and 710.7, UPC 2003. |
| 03/22/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Clarify heights for millwork, microwave, and sink for accessibility per ANSI A117.1 2003. |
| 03/27/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 03/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |