Permit Number: T07CM01135
Parcel: 137339130

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01135
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/21/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
03/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the design for the HVAC modifications: which RTU
are the return air grilles to be connected to and how will the revised air flow affect the existing air distribution system?
03/21/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. provide info on discon means for heaters 2. new circuits on pnl b-1 marked as spares 3. circuits for new sink pump not on plan
03/21/2007 ROBERT SHERRY WATER REVIEW Approved
03/21/2007 DAVE MANN FIRE REVIEW Approved
03/21/2007 JASON GREEN ENGINEERING REVIEW Approved
03/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide justification for not disposing of the sink waste by gravity. Reference Section 709.0, UPC 2003.
2. Lift stations for public use require duplex pumps along with visual and audible alarms. Reference Section 710.9, UPC 2003.
3. The 2" sanitary line for the existing service sink is too small to accomodate the discharge from the lift station (2 fixture units per 1 gpm of discharge). Reference Section 710.5, UPC 2003.
4. Provide cleanouts for the pumped discharge of the lift station. Reference Sections 707.4 and 710.7, UPC 2003.
03/22/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Clarify heights for millwork, microwave, and sink for accessibility per ANSI A117.1 2003.
03/27/2007 CAGUILA1 WWM REVIEW Needs Review
03/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review