Permit Number: T07CM00957
Parcel: 13819045B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM00957
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Correct the values of the MOCP. MCA, and the Unit Full Load Amps for the new heat pump.
06/04/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. An approved appeal to the building official is required prior to approval of the condensate drain piping.
2. The basis for the ventilation requirements using ASHRAE 62.1 is the default population of the space as shown on Table 6.1.
3. Correct the values of the MOCP. MCA, and the Unit Full Load Amps for the new heat pump.
06/04/2007 CHRIS KIEL (WILDAN) BUILDING-COMMERCIAL REVIEW Denied 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE SUPPORT MEMBERS BETWEEN THE EXISTING W12x19 BEAMS IN ORDER TO VERIFY THAT THE UNIT HAS BEEN SUPPORTED PER SECTION 106.1.1 OF THE 2003 IBC.
06/04/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed