Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM00957
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Correct the values of the MOCP. MCA, and the Unit Full Load Amps for the new heat pump. |
| 06/04/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. An approved appeal to the building official is required prior to approval of the condensate drain piping. 2. The basis for the ventilation requirements using ASHRAE 62.1 is the default population of the space as shown on Table 6.1. 3. Correct the values of the MOCP. MCA, and the Unit Full Load Amps for the new heat pump. |
| 06/04/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR THE SUPPORT MEMBERS BETWEEN THE EXISTING W12x19 BEAMS IN ORDER TO VERIFY THAT THE UNIT HAS BEEN SUPPORTED PER SECTION 106.1.1 OF THE 2003 IBC. |
| 06/04/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed |