Permit Number: T07CM00735
Parcel: 114540620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00735
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00735 3/15/07

1. Provide a disconnecting means for the heater. Reference NEC 424.19.
2. Receptacles on lighting circuit on Electrical Lighting Plan do not appear on the panel schedule load tabulation. Furthermore, similar receptacles are included in the same approximate position on the Electrical Power Plan. Clarify intent.
3. Please account for continuous load and largest motor for demand calculations. it appears that the service would now draw 680.8A, not 616.3.
03/15/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
03/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the design for the HVAC modifications: which RTU
are the return air grilles to be connected to and how will the revised air flow affect the existing air distribution system?
03/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/26/2007 FSANCHE1 WWM REVIEW Needs Review