Review Details: COMMERCIAL TI
Permit Number - T07CM00735
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/15/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00735 3/15/07 1. Provide a disconnecting means for the heater. Reference NEC 424.19. 2. Receptacles on lighting circuit on Electrical Lighting Plan do not appear on the panel schedule load tabulation. Furthermore, similar receptacles are included in the same approximate position on the Electrical Power Plan. Clarify intent. 3. Please account for continuous load and largest motor for demand calculations. it appears that the service would now draw 680.8A, not 616.3. |
| 03/15/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 03/21/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the design for the HVAC modifications: which RTU are the return air grilles to be connected to and how will the revised air flow affect the existing air distribution system? |
| 03/26/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/26/2007 | FSANCHE1 | WWM | REVIEW | Needs Review |