Permit Number: T07CM00735
Parcel: 114540620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00735
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2007 STEVE SHIELDS ZONING REVIEW Approved
02/26/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide manufacturer's equipment data along with electrical operating information for the baseboard heaters. Reference Section 301.6, IMC 2003.
3. Clarify the design and sequence of operation for the HVAC modifications; which RTU is each diffuser/return air grille to be connected to, where is the controlling thermostat, what damper is being actuated, and how will the revised air flow affect the existing air distribution system?
4. Provide calculations showing that adequate outside air is being provided to the new rooms. Reference Sections 403.3 and 403.3.2, IMC 2003.
02/26/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Resize the drainage piping from 1-1/2" to 2" to conform to the requirements of Table 7-3, Footnote 2, UPC 2003, for a public bar sink.
3. Provide an upper terminal cleanout for the sinks. Reference Section 707.4, UPC 2003.
02/26/2007 ROBERT SHERRY WATER REVIEW Approved
02/26/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
02/27/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
02/27/2007 DAVE MANN FIRE REVIEW Approved
03/15/2007 GBONILL1 WWM REVIEW Needs Review
03/15/2007 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/15/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review