Permit Number: T07CM00470
Parcel: 141090300

Address:
7960 S KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM00470
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2007 DAVE MANN FIRE REVIEW Approved
07/24/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: MER Corporation Expansion
T07CM00470
Site Plan (3rd Review)

TRANSMITTAL DATE: July 25, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. Show the proposed handicapped ramp at the proposed handicapped parking space located on the east side of the proposed building.

3. The handicapped signage shown at the west end of the proposed handicapped parking space, located on the east side of the proposed building, appears to reduce the 30" overhang for the vehicle. Clearly indicated on the plan that the 30" overhang is not reduced or relocate sign per Detail 11/C1.2.

4. Zoning is willing to provide an over the counter review once all comments above have been addressed. Please Call or email for an appointment.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\site\t07cm00470-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
07/25/2007 STEVE SHIELDS ZONING HC SITE REVIEW Denied
08/01/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. The required screen along a street frontage for vehicular use and outdoor display areas may be lowered to thirty (30) inches if the site is located:

§ On a street that is not designated as an MS&R; and
§ Across the street from nonresidential uses or unimproved, non-residentially zoned parcels

2. A 30" continuous screen along street frontages for vehicle use area must be provided per LUC Table 3.7.2-I. Identify the location of screening elements on landscape plan.
08/02/2007 ANDREW CONNOR NPPO REVIEW Approved
08/15/2007 MATT FLICK ENGINEERING REVIEW Approved Site plan approval for Phase 1 only. Previous Phase 1 comments have been addressed.
08/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Third request. Provide the rim elevation of the next upstream sanitary manhole Determine the need for a backwater valve per Section 710.1, UPC 2003.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2007 GERARDO BONILLA APPROVAL SHELF Completed
08/30/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
08/30/2007 GERARDO BONILLA REJECT SHELF Completed