Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t07cm00464 2/27/06 1. At 12500 VA per phase, Ckt DIST-35,37 would carry 120 A, which exceeds the capacity of the 60A circuit. 2. With computed VA values, Panel DIST would draw about 1000A, exceeding its capacity and that of the service. 3. At 15000 VA per phase, Ckt DIST-38,40,42 would carry 125 A, which exceeds the capacity of the 60A circuit. |
03/02/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
03/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/02/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/02/2007 | ROBERT SHERRY | WATER | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/02/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |