Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM00464
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t07cm00464 2/27/06 1. At 12500 VA per phase, Ckt DIST-35,37 would carry 120 A, which exceeds the capacity of the 60A circuit. 2. With computed VA values, Panel DIST would draw about 1000A, exceeding its capacity and that of the service. 3. At 15000 VA per phase, Ckt DIST-38,40,42 would carry 125 A, which exceeds the capacity of the 60A circuit. |
| 03/02/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
| 03/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/02/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/02/2007 | ROBERT SHERRY | WATER | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/02/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |