Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T07CM00464
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00464 2/7/07 1. Registrant's seal and signature are illegible. 2. Electrical drawings shall be on same size as site drawings, that is, full-sized not letter sized. 3. Provide an electrical site diagram showing the location of the existing panel, and the new sub-panel. 4. Provide a disconnecting means at the Modular Office. Reference NEC 225.31, 225.32. 5. Provide grounding according to the requirements on NEC 250.32 Second Building or Structure. 6. Indicate depth of conduit fill. 7. Provide available fault current, fault calculations, and fault current rating of new sub-panel. |
| 02/27/2007 | FSANCHE1 | WWM | REVIEW | Needs Review | |
| 02/27/2007 | FSANCHE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 02/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 02/27/2007 | FSANCHE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/27/2007 | FSANCHE1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2007 | FSANCHE1 | OUT TO CUSTOMER | Completed |