Permit Number: T07CM00183
Parcel: 12111022A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM00183
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/31/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. It appears that the Main Bonding Jumper should be sized at 500 KCMIL on Sheet E-501, Detail 5.
2. CU-4 is to be relocated from EDP-1 to MDP-2 according to the Electrical Demo, Sheet ED-701. Such equipment is on EDP-2 panel schedule and new Line Diagram. Please clarify.
3. Please specify the fault current rating at ATS-2 and MTS-2, considering the magnitude of F11 and F12.
02/09/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/21/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide structural calculations to justify slab design (detail 6/C-507) for 67,549 lb. generator.
2) Text hgt. on all drawings shall be a minimum of 1/8" in hgt.