Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM00183
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2007 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/31/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. It appears that the Main Bonding Jumper should be sized at 500 KCMIL on Sheet E-501, Detail 5. 2. CU-4 is to be relocated from EDP-1 to MDP-2 according to the Electrical Demo, Sheet ED-701. Such equipment is on EDP-2 panel schedule and new Line Diagram. Please clarify. 3. Please specify the fault current rating at ATS-2 and MTS-2, considering the magnitude of F11 and F12. |
| 02/09/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 02/21/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide structural calculations to justify slab design (detail 6/C-507) for 67,549 lb. generator. 2) Text hgt. on all drawings shall be a minimum of 1/8" in hgt. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 02/27/2007 | SUE REEVES | REJECT SHELF | Completed |