Permit Number: T07BU02194
Parcel: 11807003D

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU02194
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2008 LOREN MAKUS ENGINEERING REVIEW Denied DATE: September 4,2008

To: Andie Haslem
Engineering and Environmental Consultants, Inc
4625 East Fort Lowell Road
Tucson, Arizona 85712

FROM: Loren Makus
Engineering Division

SUBJECT: Lucky Wishbone
Grading Plan T07BU02194 (Secon Review)
T14S, R13E, Section 22

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP), Drainage Report (DR) and Stormwater Pollution Prevention Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

The grading plan can be approved once the SWPPP can be approved.

Stormwater pollution prevention plan:


1. I strongly recommend that the SWPPP be examined more carefully before submission for review. The submitted SWPPP contains 3 copies of the general permit, for example.
2. Additionally, where information is required but not yet known, such as for names of operators, leave space for the information to be filled in when it becomes known.
3. On the site map clearly identify where stormwater is discharged from the site.
4. Page 7 refers to the plans in appendix A. Provide the correct reference. The page also indicates that the plan is preliminary. Provide a plan that indicates what is to be implemented at the site.
5. The checklist indicates that the inspector's qualifications are listed on page 10 of the SWPPP. They are not there. Provide the qualifications.
6. The checklist was requested in order to expedite the review of the SWPPP. Please make sure the checklist is correct.
7. The SWPPP provided is full of extraneous material and lacking in specificity. Please revise the SWPPP to be specific without the extraneous material.


If you have any questions, I can be reached at (520) 837-4927 or loren.makus@tucsonaz.gov
Loren Makus, EIT
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4927
(520) 879-8010 fax
C:/Address Grading
09/04/2008 DAVID RIVERA ZONING REVIEW Approved
09/05/2008 ANDREW CONNOR NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2008 DELMA ROBEY OUT TO CUSTOMER Completed
09/08/2008 SUE REEVES REJECT SHELF Completed