Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T07BU01526
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Fire Central T07BU01526 Grading Plan (1st Review) TRANSMITTAL DATE: August 2, 2007 1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal. 3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t07bu01526 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents |
| 08/14/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Site plan approval is necessary to continue review. Ensure that all changes to the site plan are reflected on the grading plan. |
| 08/20/2007 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | August 31, 2007 T07CM03015, T07OT01635, T07OT01526 FIRE CENTRAL 495 W Cushing Street Site, Grading and Floodplain Reviews The plans cannot be approved as submitted. The following comments must be addressed on each plan as applicable. 1. Provide an exhibit in the Drainage Report showing the existing and proposed floodplain boundaries. All areas subject to periodic inundation must be identified. 2. Revise the site plan to delineate the floodprone areas. The site plan should show the areas subject to inundation under existing condition and show the areas that will still be subject to periodic inundation once the improvements have been completed. 3. Provide existing and future water surface contours for all off-site and on-site concentrated flows. (Ensure that the lowest floor of each structure is at least one foot above the adjacent water surface contours.) 4. Provide sufficient spot elevations details to show that the underground parking garage will be kept flood-free. The floodplain use permit and SWPPP will be approved when the site and grading plans are approved. If you have any questions or want to set up a meeting contact me at 520.837.4927 or loren.makus@tucsonaz.gov. Loren Makus Senior Engineering Associate |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/04/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |