Permit Number: T07BU01158
Parcel: 14103024C

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T07BU01158
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: July 11, 2007
ACTIVITY NUMBER: T07BU01158
PROJECT NAME: RV Storage Facility
PROJECT ADDRESS: 6401 East Old Vail Road
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: 3 COPIES OF THE GRADING PLAN AND SWPPP

APPROVED: DRAINAGE REPORT

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. Show the grading limits on the plan. See the Development Standard 11-01.9. for the required setbacks.

The above comment is from the previous review and has not been adequately addressed. The grading limits can not extend out to the adjacent properties. Revise the grading plan appropriately. Refer to the Development Standard 11-01.9. for the required setback information.

3. It is acknowledged description is provided in the site plan keynote 17. However there is not a detail for the outlet of the bleeder pipe. Provide another detail of the outlet for the bleeder pipe and the rock riprap. Also on the grading plan indicate where the detail can be found for the bleeder pipe inlet.

The above comment is from the previous review and has not been fully addressed. Provide reference to the details found on sheet 5 in keynote 17.

4. Provide cross sections for the east and south side of the property. The cross section should include the property line, some grades, PAAL and sidewalk dimensions, walls, fences, etc.

The above comment is from the previous review and has not been adequately addressed. Revise detail D/C-3 to show the property line rather than a building.


SWPPP COMMENTS

1. Once the grading plan is close to approval submit 3 copies of the SWPPP and grading plan.

2. Each operator is responsible for submitting a completed NOI to ADEQ and a copy to the City of Tucson. Both of the NOIs submitted (Appendix A) have not e been filled out. Provide copies of both NOIs filled out and signed by the owner and the contractor. (Part IV.F)

3. The Owner and Operator (1) certification statement needs to be signed prior to approval of the SWPPP. This assures the City of Tucson prior to issuance of a grading permit that there is a designated responsible party for the SWPPP.
07/12/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: RV Storage Facility
T07BU01158
Grading Plan

TRANSMITTAL DATE: July 12, 2007

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
07/16/2007 GERARDO BONILLA REJECT SHELF Completed