Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T07BU00155
Review Name: TANKS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/01/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | 1.) The governing Fire Code is the 2003 IFC. 2.) Indicate a "deadman" switch on dispenser. 3.) Indicate which fuel is in which tank. (Only Class II and Class IIIA liquids can be stored in the 20,000 gallon tank. IFC Section 2206.2.4.2, i.e., the Jet A fuel) 4.) Need cut sheets on all components, including tank, type of piping, relief valves, dispensers, overfill protection, spark arrestors, etc. 5.) Add note indicating appropriate signage will be installed. 6.) Indicate where sump pump discharges. 7.) Bollards are shown at 5' on center. Code states 4' maximum. 8.) Drawings should be drawn to scale. Unable to verify minimum 3' between tanks required by code. 9.) Indicate on plan that relocated tank will be inerted before relocation, and new pressure test will be performed. 10.) Separate permit form for Fire Department needs to be completed. (attached) |
02/01/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1) PROVIDE STRUCTURAL CALCULATIONS FOR IMPOSED LOADS ON FOUNDATION. 2) PROVIDE TANK TO FOUNDATION ATTACHMENT DETAILS. 3) CLARIFY/DETAIL HOW SHADE STRUCTURE PARTIAL DEMO AND RELOCATION OF END WALL IS BEING DONE. NEW STRUCTUAL CALCS FOR WIND AND SEISMIC WILL BE REQUIRED. |
05/08/2007 | DROBEY1 | ZONING | REVIEW | Needs Review |