Plan Number: T06PI00041
Parcel: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T06PI00041
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2006 TAMI HAUSER ENGINEERING REVIEW Needs Review
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COT STREETS DIVISION Denied SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES PC WASTEWATER MGMT Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES QUEST COMMUNICATION Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES COX COMMUNICATION Denied SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES SOUTHWEST GAS CORP Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES EL PASO NATURAL GAS Completed SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/28/2006 TAMI HAUSER UTILITY CLEARANCES KINDER MORGAN ENERGY Denied SUBMIT UTILITY LETTERS FOR CITY OF TUCSON STREETS DIVISION, COX COMMUNICATIONS, AND KINDER MORGAN.
10/31/2006 GARY WITTWER DOT LANDSCAPE REVIEW Approved
11/14/2006 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
11/27/2006 Estevan Tineo DOT ENGINEERING REVIEW Denied November 27, 2006: T06PI00041 (Sunnyside Elementary School):

1. Is the public sewer part of this project a separate submittal or is it part of this plan? If it is, then the Pima County Waste Water signature line should be provided on the cover sheet and the corresponding PCWW plan number.
2. Sheet 2 of 3: Provide pedestrian access easements, for public pedestrian access, at the two proposed access ramps located at Sun View Way.
3. Sheet 2 of 3: Note 7 indicates new sidewalk and the plan view shows 4' sidewalk? According to the City Development Standards, 5' sidewalk is required. Why is 4' sidewalk proposed? Revise accordingly.
4. Sheet 3 of 3: Detail 3 of 3 does not represent the proposed sidewalk location. This detail indicates a "shy" space between curbing and sidewalk. However, Detail 1 of 3 indicates sidewalk against vertical curbing? Please revise detail accordingly.
5. Sheet 3 of 3: Detail 6 of 3 is confusing. The detail seems to indicate concrete gutter, and is not clear where the landing starts? Please revise detail to indicate ramp grades, landing area, and other items as needed to detail proposed ramps. In addition please indicate r/w line.
6. Sheet 3 of 3: Based on the plan view, Detail 5 of 3 is not sufficient to detail these ramps. Please provide a detail for each ramp detailing specific issues (pedestrian access) at each ramp.
11/28/2006 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
11/28/2006 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed