Review Details: FLOODPLAIN
Permit Number - T06OT02523
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Denied | The proposed structure is located in an area characterized by shallow sheet flooding during the regulatory 100-year flood. Therefore, the lowest finished floor elevation of the new structure is a minimum 1.5 feet above highest adjacent grade, not 0.5 feet as shown on the plans. Please revise the plans to show the minimum floor elevation is in compliance with floodplain regulations. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/21/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 11/21/2006 | SUE REEVES | REJECT SHELF | Completed |