Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06EL01692
Parcel: 13213062A

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T06EL01692
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06EL01692 8/24/06

1. Since the service entrance capacity is 1200A according to the line diagram, it appears that the AFC from TEP is 75,100A, not 55,600A.
2. Please document that this expansion involves storage only of paint supplies, and does not involve any opening of cans/mixing of contents.
3. Applicant shall have Mechanical and Building added to this Permit, or demonstrate that a new 3/4 HP Evap added to the roof has been approved under separate permit.