Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T06EL00306
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/17/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T06EL00306 2/15/06 1. It is unclear why there are (3) 3/0 going to each disconnect from the gutter, and going from each disconnect to the pullbox, regardless of whether such disconnect is 3/P or 2/P. 2. Please remove the redundant #4 GND in the conduits between the gutter and the new disconnects. 3. Please remove the redundant 1/0 GND between the CT can and the gutter. 4. Provide TEP available fault current, rating of equipment, and fault calculations as necessary. 5. Clarify where the underground feeders are going to. Necessary to continue review per NEC 250.32, 225 Part II, and any other code sections which may apply. It may be useful to discuss this with the Electrical Plans Examiner at 791.5550 X1106. |