Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T06CM06406
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the expansion loop installation requirements from the pipe manufacturer with the details on sheet M1.2. 2. Provide a detail for the concrete thrust blocks noted on sheet M1.1 . 3. Confirm the expansion/contraction requirements for the CHW piping. If compression of the insulation is to be used to accomodate the pipe movement, how much will the insulating capability be degraded? |