01/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Fill in the electrical load on panel schedule for Ckt RP-24, the Safe.
2. Considering continuous loading for lighting, it appears that loads on Phases A, B, and C are 16,830 VA, 16,770 VA, and 14,570 VA, respectively, for an aggregate amperage of 133.81A, not 108.08A.
3. Panel schedules difficult to read. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
12/07/2006 DAVE MANN FIRE REVIEW Approved
12/07/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/11/2006 RSHERRY1 WWM REVIEW Passed
12/11/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/11/2006 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2006 ROBERT SHERRY WATER REVIEW Approved
12/19/2006 LINHART PETERSEN POERS ASSOC. BUILDING-COMMERCIAL REVIEW Approved