Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM06201
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Fill in the electrical load on panel schedule for Ckt RP-24, the Safe. 2. Considering continuous loading for lighting, it appears that loads on Phases A, B, and C are 16,830 VA, 16,770 VA, and 14,570 VA, respectively, for an aggregate amperage of 133.81A, not 108.08A. 3. Panel schedules difficult to read. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. |
| 12/07/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/07/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 12/11/2006 | RSHERRY1 | WWM | REVIEW | Passed | |
| 12/11/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/11/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/11/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/19/2006 | LINHART PETERSEN POERS ASSOC. | BUILDING-COMMERCIAL | REVIEW | Approved |