Permit Number: T06CM06098
Parcel: 12213035B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM06098
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2007 CAGUILA1 ZONING REVIEW Needs Review
01/19/2007 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
01/19/2007 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/19/2007 SDISHRO1 WATER REVIEW Needs Review
01/19/2007 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
01/19/2007 CAGUILA1 WWM REVIEW Needs Review
01/19/2007 MARTIN BROWN FIRE REVIEW Approved
01/19/2007 CAGUILA1 ENGINEERING REVIEW Needs Review
01/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM06098 11/29/06

1. Panel schedule has VA loads not associated with any circuit.
2.
3. Provide fault calculations for new panel.
4. The note regarding current limiting breakers has a revision triangle. No such revision documented.
5. Indicate amperage rating of new panel.