Review Details: COMMERCIAL TI
Permit Number - T06CM06098
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 01/19/2007 | CAGUILA1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/19/2007 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 01/19/2007 | SDISHRO1 | WATER | REVIEW | Needs Review | |
| 01/19/2007 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 01/19/2007 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 01/19/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/19/2007 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
| 01/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/29/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T06CM06098 11/29/06 1. Panel schedule has VA loads not associated with any circuit. 2. 3. Provide fault calculations for new panel. 4. The note regarding current limiting breakers has a revision triangle. No such revision documented. 5. Indicate amperage rating of new panel. |