Permit Number: T06CM06019
Parcel: 138240860

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T06CM06019
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2007 DAVE MANN FIRE REVIEW Approved
11/29/2007 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments.
11/29/2007 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T06CM06019
1501 W. Commerce Ct.
Site Plan Revision

TRANSMITTAL DATE: 11/29/07

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The location of the truncated domes as indicated on the revised handicap ramps at the cross walks are incorrect. A 24" in depth strip of truncated domes is required on the landing adjacent to the crosswalk. Required to be revised in 3 locations.

2. The landings for the revised handicap ramps must be physically separated from the vehicular use area. Clearly indicate that the 6" extruded curb is located around the landing except at the crosswalk junction to the landing.

3. Revise the parking space calculation in the zoning code review portion of sheet x1.1. The number of required parking spaces is still 113 but the number of provided parking spaces is 114.

4. Coordinate the above required changes with the submitted revised grading plan.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T06CM06019.doc
12/04/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied The revised site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape & grading plan.
12/06/2007 ANDREW CONNOR NPPO REVIEW Approved
12/12/2007 JASON GREEN ENGINEERING REVIEW Denied DATE: December 13, 2007
SUBJECT: COPE Behavioral Services Engineering Review- Revised Site Plan and Grading Plan
TO: Reliable Permits
LOCATION: 1501 W Commerce CT, T15S R13E Sec15 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T06CM06019 (Site Plan) and T07BU01592 (Grading Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan and grading plan for the required field revisions. The site plan and grading plan are not approved at this time. Please address the following comments:

SITE PLAN COMMENTS: (Sheet X1.1)

1) DS Sec.2-02.2.1.A.12: Revise the location of the truncated domes as indicated on the revised site plan. The truncated dome location at the revised handicap ramps at the crosswalks are incorrect (refer to Sheet X1.1 of the last approved site plan for correct locations). A 24" in depth strip of truncated domes are required at the transition of the pedestrian circulation and vehicular use area adjacent to the crosswalk.
2) DS Sec.2-02.2.1.A.12: Verify that the landing for the revised handicap ramps is physically separated from the vehicular use area. Clearly indicate that the 6" extruded curb is located around the landing except at the crosswalk intersection to the landing.

GRADING PLAN COMMENTS: (Sheet C-2)

3) DS Sec.2-02.2.1.A.12: Revise the location of the truncated domes as indicated on the revised site plan. The truncated dome location at the revised handicap ramps at the crosswalks are incorrect (refer to Sheet X1.1 of the last approved site plan for correct locations). A 24" in depth strip of truncated domes are required at the transition of the pedestrian circulation and vehicular use area adjacent to the crosswalk.
4) DS Sec.2-02.2.1.A.12: Verify that the landing for the revised handicap ramps is physically separated from the vehicular use area. Clearly indicate that the 6" extruded curb is located around the landing except at the crosswalk intersection to the landing.

GENERAL COMMENTS:

Please provide a revised site plan and revised grading plan that address the comments provided above. For expedite purposes the site plan can be reviewed over the counter (DSD Engineering Division comment only) for stamp approval once all items have been addressed. The revised grading plan must be reviewed in house in order to digitize the revised plan and get it to our Records Department.

For any questions or to schedule a meeting, call me at 791-5550, extension 1189.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
Development Services
12/14/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2007 VFLORES1 OUT TO CUSTOMER Completed
12/17/2007 VFLORES1 REJECT SHELF Completed