Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T06CM05984
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project (31 fixture units equates to a demand of 21 GPM). Note that Tucson Water does not provide 3/4" meters. |
| 11/07/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/08/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/14/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |
| 11/14/2007 | THAUSER1 | REJECT SHELF | Completed |