Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM05782
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
06/18/2007 ROBERT SHERRY WATER REVIEW Denied 1. Tucson Water will no longer allow water meters to be manifolded to achieve additional capacity.
2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
06/19/2007 DAVE MANN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
06/20/2007 LOREN MAKUS ENGINEERING REVIEW Approved
06/21/2007 TERRY STEVENS ZONING REVIEW Denied 06/20/07

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The gross floor area indicated on the floor plans (80,527 sq. ft. ground level, 11,070 sq. ft. mezzanine level) when totaled does not equal the square footage indicated in the site/building data, on page DP-1, for Anchor #2.

Revise the proposed site and building data portion indicated on DP-1 to include the additional square footage of Anchor #2

Provide a new parking calculation (required parking) for the entire shopping center based on the additional square footage of GFA for Anchor #2.

FYI: parking calculations are based on gross floor area (GFA) of each structure not on the square footage of the foot print of the structure.

The new parking calculation and site/building data will be attached to the site plan held by the City of Tucson and will be used to verify changes when the revised development plans are submitted at a future date.
06/27/2007 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2007 SUE REEVES OUT TO CUSTOMER Completed