Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T06CM05771
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2006 | DAVE MANN | FIRE | REVIEW | Denied | Please add the following automatic sprinkler criteria to the plans: 1. The hazard classification of the occupancy including any special hazards. 2. The design standard to be used. 3. The availability and adequacy of the water supply. 4. The design density and the area of operation. |
| 11/09/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/09/2006 | BETSY COTTLE | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/15/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide energy code compliance calculations. Reference Section 101.4, International Energy Conservation Code 2003. |
| 11/16/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the "drain trough" detail referenced on sheet M1.0. Clarify how (or if) this relates to the 10" storm drain (with seven 4" roof drains attached) shown on sheet C1. Reference Section 103.2.3, UPC 2003. 2. Coordinate the water service for the building and for irrigation use with sheet C1. Show the location and size of the backflow preventor and the meter. Reference Section 103.2.3, UPC 2003. 3. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 710.1, UPC 2003. |
| 11/16/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/20/2006 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Chicanos Por La Causa - Retail 305 W. Irvington Road T06CM05771 Building Plan (1st Review) TRANSMITTAL DATE: November 20, 2006 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180. C:\planning\grading\t06cm05771.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plan and additional requested documents |
| 11/29/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
| 11/30/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/01/2006 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Denied | November 30, 2006 City of Tucson Development Services 201 N. Stone Avenue Tucson, AZ 85701 RE: CHICNOS POR LA CAUSA SHELL – 1ST REVIEW CITY OF TUCSON LOG NO. T06CN05771 WILLDAN PROJECT NO. 13881-6082 The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable. This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan. Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel. Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms M 330* VB 10,200 Yes No Special Inspection is required for the following items: Field Welding Expansion/Epoxy anchors The following items are acceptable for deferred submittals: Wood I-Joists GENERAL COMMENTS: General A signed special inspection form from the City of Tucson is required at the time that the plans are resubmitted for a back check. Reference the City of Tucson Submittal Policy. A deferred submittal letter for wood I-Joists will need to be forwarded directly to the Building Official and approved prior to the plans being delivered to the City. Reference the City of Tucson Submittal Policy. ARCHITECTURAL COMMENTS: Sheet T1.0 Please revise the occupant load calculation to use 30sf/occupant per table 1004.1.2 of the 2003 IBC. Sheet A0.1 Please specify the distance from the rear of the building to the property line in order to verify compliance with table 602 of the 2003 IBC. Sheet A2.0 Please specify the location of safety glazing in order to verify compliance with section 2406 of the 2003 IBC. It is suggested to provide information regarding the door hardware in order to verify compliance with section 1008.1.8.3 of the 2003 IBC as opposed to addressing this issue during the future tenant improvements. Please provide a COMcheck for the building envelope in order to verify compliance with section 2003 IECC. In addition, please specify on the plans the U-values for the doors and windows. Sheet A6.0 Please coordinate the information regarding the installation of the mechanical units between the architectural, structural and mechanical sheets per section 106.1.1 of the 2003 IBC. The current submittal denotes the installation of the units in the mechanical sheets, but the architectural and structural sheets denote differently. Please provide permanent access to the rooftop mechanical units in accordance with section 306.5 of the 2003 IMC. In addition, please provide additional information for the ladder assembly for access between the different roof areas to verify compliance with section 306.5 of the 2003 IMC. STRUCTURAL COMMENTS: Sheet S2.0 Please verify the use of detail 104 at the porch columns per section 106.1.1 of the 2003 IBC. In addition, please specify where details 108 and 109 are used. Sheet S3.0 Please specify the mechanical unit locations and weights on the roof-framing plan per section 106.1.1 of the 2003 IBC. Please coordinate the size of LT3 between the structural calculations and the plans per section 106.1.1 of the 2003 IBC (1/4” vs. 3/16”). PLUMBING COMMENTS: Please refer to the City’s comments. MECHANICAL COMMENTS: Please refer to the City’s comments. ELECTRICAL COMMENTS: Reviewed and approved by the City of Tucson. ENERGY CODE COMMENTS: Reviewed and accepted. ACCESSIBILITY COMMENTS: Reviewed and accepted. Sincerely, WILLDAN Martin Haeberle, C.B.O. Building Official MAH/tb |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/01/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/01/2006 | SUE REEVES | REJECT SHELF | Completed |