Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T06CM05246
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/03/2006 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/03/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/03/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Directly connect the mop sink, hand sink, waiter's station sink, and the grease trap effluent. 2. Provide a vent to protect the grease trap. 3. Show that the air admittance valve on the flow control device is specifically listed for that application by both the manfacturer of the flow control device and the air admittance valve manufacturer. 4. Provide traps for the hand sink and the two directly-connected compartments of the 3-compartment sink. |
10/03/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/03/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Clarify / justify fixture count is adequate for the removal of restroom. |
10/03/2006 | ANY | ENGINEERING | REVIEW | Approved | |
10/10/2006 | JWILLIA5 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
10/10/2006 | GBONILL1 | WWM | REVIEW | Needs Review | |
10/10/2006 | GBONILL1 | FIRE | REVIEW | Needs Review | |
10/10/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |