Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM05246
Parcel: 124050590

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T06CM05246
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2006 STEVE SHIELDS ZONING REVIEW Approved
10/03/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/03/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Directly connect the mop sink, hand sink, waiter's station sink, and the grease trap effluent.
2. Provide a vent to protect the grease trap.
3. Show that the air admittance valve on the flow control device is specifically listed for that application by both the manfacturer of the flow control device and the air admittance valve manufacturer.
4. Provide traps for the hand sink and the two directly-connected compartments of the 3-compartment sink.
10/03/2006 ROBERT SHERRY WATER REVIEW Approved
10/03/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Clarify / justify fixture count is adequate for the removal of restroom.
10/03/2006 ANY ENGINEERING REVIEW Approved
10/10/2006 JWILLIA5 ELECTRICAL-COMMERCIAL REVIEW Passed
10/10/2006 GBONILL1 WWM REVIEW Needs Review
10/10/2006 GBONILL1 FIRE REVIEW Needs Review
10/10/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review