Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T06CM04619
Parcel: 112072890

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04619
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2006 STEVE SHIELDS ZONING REVIEW Approved
11/03/2006 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T06CM04619

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

As of 9-02-04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the 2003 UPC with amendments. All plans should reference these codes. See this site for all adopted amendments: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

SITE PLAN:

1. Provide a note for: Underground facility tracer wires per DSD Memo, 10/24/2005.

STRUCTURAL PLANS:

1. Justify the design criteria (sheet #5) for the roof dead load of 10 psf. This may be correct for the carport area without ceiling, but the joist with gypsum board will add 5 psf in the living areas.
2. Where the roof pitch is less than 3:12 the ridge member shall be designed as a beam, R802.3. A GluLam ridge beam may be considered. In this case rafters of 2 x 6 @ 24" are correct with joists of 2 x 8 @ 24" or 2 x 6 @ 16".
3. Show the ventilation opening (22" x 30") between attic areas at the over framing location on the Section sheet #6.

ELECTRICAL PLANS:

1. The kitchen countertop receptacle outlet (ckt #13) requires ground fault circuit interrupting protection, E3802.6.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.
11/08/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved