Permit Number: T06CM04583
Parcel: 137090090

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T06CM04583
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2006 ANY ZONING REVIEW Active
08/15/2006 ANY WWM REVIEW Active
08/15/2006 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
08/15/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
08/25/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T06CM04583 8/25/06

1. Provide a disconnecting means for the Water Heater according to the requirements of NEC 422 Part III. These units do not plug in to duplex receptacles.
2. Provide specifications for new Water Heater, including electrical requirements.
08/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show that the ventilation for this space complies with the requirements of Section 403.3, IMC 2003.
08/25/2006 MARTIN BROWN FIRE REVIEW Approved
08/25/2006 ROBERT SHERRY WATER REVIEW Approved
08/25/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide for the minimum plumbing fixtures for business occupancy (i.e. drinking fountain). Refererence Section 2900, IBC 2003.
2. Provide a riser diagram for waste and vent.
3. Provide a specification for the new water heater.
08/25/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. PROVIDE COMPLETED CODE REVIEW CHECKLIST, SEE DSD WEBSITE AT <www.tucsonaz.gov/dsd>, ONLINE SEVICES, SHOW SEPARATED/NON-SEPARATED W/FIRE-RATED WALL,IF REQUIRED.
S2. PROVIDE SITE/LOCATION PLAN WITH PROPERTY LINES SHOWN AND ANNOTATED, SHOWING FIRE-RATED WALLS, SHOWING ADJACENT TENANT OCCUPANCY AND DIMENSIONALLY LOCATING BUILDING AND TENANT SPACE ON SITE.
S3. THIS PROJECT APPEARS TO BE A CHANGE OF OCCUPANCY AND AS SUCH THIS TENANT SPACE MUST BE BROUGHT INTO CONFORMANCE WITH THE 2003 IBC AND ANSI A117.1-2003 ed.
S4. RESOLVE EXPIRED PERMITS LISTED:
1.T01OT00518. #180
2.T98BU01549.
3.T98CM00721.
4.T01OT00519. #100
5.T03EL00098. #100
6.T04EL01077. #100
7.T01OT00521. #120
8.T01EL02476. #160
9.T01OT00520. #160