Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/27/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Document existing conduits as such. 2. On the Inverter Layout, reword the label on the Disconnect Switch to read: "MAIN SERVICE DISCONNECT LOCATED IN BUILDING 40' SOUTH ROOM #117. 3. Provide overcurrent protection for the conductor from the sub-panel to the AC main. 4. Provide load calculations sufficient to demonstrate that the electrical load connected to the AC Main does not exceed 140A. 5. Provide a large-font sized note on the plans citing reference to the TEP model drawings. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/25/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
01/25/2007 | SUE REEVES | REJECT SHELF | Completed |