Permit Number: T06CM04165
Parcel: 110034830

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM04165
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Document existing conduits as such.
2. On the Inverter Layout, reword the label on the Disconnect Switch to read: "MAIN SERVICE DISCONNECT LOCATED IN BUILDING 40' SOUTH ROOM #117.
3. Provide overcurrent protection for the conductor from the sub-panel to the AC main.
4. Provide load calculations sufficient to demonstrate that the electrical load connected to the AC Main does not exceed 140A.
5. Provide a large-font sized note on the plans citing reference to the TEP model drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2007 DELMA ROBEY OUT TO CUSTOMER Completed
01/25/2007 SUE REEVES REJECT SHELF Completed