Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T06CM04042
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/20/2013 | MARTIN BROWN | FIRE | REVIEW | Denied | East wall on sheet T.1, T.2, D.1, & S.2 does not look the same on all sheets. Please resolve. Buildings 2 & 3 now total 13,817 square feet of F-1 occupancy. Per section 903.2.4 of both the 2012 IBC and IFC, this project requires fire sprinklers. |
| 10/01/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T.2; CODE REVIEW AND SITE PLAN: THE PLUMBING FIXTURE TABLE INDICATES 42 OCCUPANTS IN THE S-2 AREA, AND 104 OCCUPANTS IN THE F-1 AREAS (146 TOTAL). FROM THE PLAN, THERE ARE 15 OCCUPANTS + 42 + 14 + 3 = 74 OCCUPANTS IN THE F-1 AREAS AND 43 OCCUPANTS IN THE S-2 AREA (117 TOTAL). CLARIFY THE OCCUPANT LOAD. 2. SHEET T.2; CODE REVIEW AND SITE PLAN: IN THE EGRESS WIDTH CALCULATIONS FOR THE THREE BUILDINGS, THE OCCUPANT LOAD IS LISTED AS 31 + 73 + 47 = 151 TOTAL. CLARIFY THE OCCUPANT LOAD. 3. SHEET S.1 (FOUNDATION NOTES); STRUCTURAL CALCULATIONS (COVER SHEET): THE CALCULATIONS INDICATE A 2500 PSF BEARING VALUE, WHILE THE DRAWINGS INDICATE 1500 PSF. CLARIFY. 4. SHEET S.2; BUILDING REFERENCE PLAN: ON GRID F, TRUSSES 202A AND 202B ARE INDICATED. WHAT IS THE DIFFERENCE? PROVIDE A NOTE ON THE DRAWING. 5. SHEET S.3 (TRUSS 201); STRUCTURAL CALCULATIONS (SHEET 6): IT APPEARS THE VERTICAL TRUSS MEMBER ON THE CALCULATIONS IS A 1 1/2 X 1 1/2 X 1/4, WHILE THE TRUSS PROFILE ON THE DRAWINGS INDICATES A 1 1/4 X 1 1/4 X 1/4. VERIFY. 6. SHEET S.3 (TRUSSES 202 AND 203); STRUCTURAL CALCULATIONS (SHEET 16): IT APPEARS THE TOP AND BOTTOM TRUSS MEMBERS ON THE CALCULATIONS ARE 2 1/2 X 2 X 3/16, WHILE THE TRUSS PROFILE ON THE DRAWINGS INDICATES 2 X 2 X 3/16. VERIFY. 7. SHEET S.3; TRUSSES 202 AND 203: NOTE 4 INDICATES A 3/4" DIAMETER BAR OCCASIONALLY-NOT CONSISTENT. PROVIDE THE INFORMATION ON THE DRAWING TO INDICATE WHAT THE "OCCASIONALLY" REFERENCES. 8. SHEET S.3; DETAIL 204: PROVIDE A DETAIL ON THE DRAWING INDICATING HOW THE C9 AND W10 ARE CONNECTED. 9. SHEET S.4; DETAIL 206: INDICATE NOTE 5 ON THE DETAIL. 10. SHEET A.1; BUILDINGS 1, 2, AND 3 FLOOR PLANS: FOR STORAGE RACKS OVER 6' IN HEIGHT UP TO 12', PROVIDE A DETAIL ON THE DRAWINGS FOR THE CONNECTION OF THE RACKS TO THE FLOOR. 11. SHEET A.1; BUILDING 1 FLOOR PLAN: CLEAR UP THE VERBIAGE AND DIMENSIONS IN OFFICE 05. 12. SHEET A.1; KEYNOTES: NOTES 15, 18, AND 22 WERE NOT LOCATED ON THE PLANS. VERIFY. 13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/09/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 10/09/2013 | CPIERCE1 | REJECT SHELF | Completed |