Permit Number: T06CM04042
Parcel: 12418187B

Address:
1401 E 20TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T06CM04042
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/20/2013 MARTIN BROWN FIRE REVIEW Denied East wall on sheet T.1, T.2, D.1, & S.2 does not look the same on all sheets. Please resolve.
Buildings 2 & 3 now total 13,817 square feet of F-1 occupancy. Per section 903.2.4 of both the 2012 IBC and IFC, this project requires fire sprinklers.
10/01/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T.2; CODE REVIEW AND SITE PLAN: THE PLUMBING FIXTURE TABLE INDICATES 42 OCCUPANTS IN THE S-2 AREA, AND 104 OCCUPANTS IN THE F-1 AREAS (146 TOTAL). FROM THE PLAN, THERE ARE 15 OCCUPANTS + 42 + 14 + 3 = 74 OCCUPANTS IN THE F-1 AREAS AND 43 OCCUPANTS IN THE S-2 AREA (117 TOTAL). CLARIFY THE OCCUPANT LOAD.
2. SHEET T.2; CODE REVIEW AND SITE PLAN: IN THE EGRESS WIDTH CALCULATIONS FOR THE THREE BUILDINGS, THE OCCUPANT LOAD IS LISTED AS 31 + 73 + 47 = 151 TOTAL. CLARIFY THE OCCUPANT LOAD.
3. SHEET S.1 (FOUNDATION NOTES); STRUCTURAL CALCULATIONS (COVER SHEET): THE CALCULATIONS INDICATE A 2500 PSF BEARING VALUE, WHILE THE DRAWINGS INDICATE 1500 PSF. CLARIFY.
4. SHEET S.2; BUILDING REFERENCE PLAN: ON GRID F, TRUSSES 202A AND 202B ARE INDICATED. WHAT IS THE DIFFERENCE? PROVIDE A NOTE ON THE DRAWING.
5. SHEET S.3 (TRUSS 201); STRUCTURAL CALCULATIONS (SHEET 6): IT APPEARS THE VERTICAL TRUSS MEMBER ON THE CALCULATIONS IS A 1 1/2 X 1 1/2 X 1/4, WHILE THE TRUSS PROFILE ON THE DRAWINGS INDICATES A 1 1/4 X 1 1/4 X 1/4. VERIFY.
6. SHEET S.3 (TRUSSES 202 AND 203); STRUCTURAL CALCULATIONS (SHEET 16): IT APPEARS THE TOP AND BOTTOM TRUSS MEMBERS ON THE CALCULATIONS ARE 2 1/2 X 2 X 3/16, WHILE THE TRUSS PROFILE ON THE DRAWINGS INDICATES 2 X 2 X 3/16. VERIFY.
7. SHEET S.3; TRUSSES 202 AND 203: NOTE 4 INDICATES A 3/4" DIAMETER BAR OCCASIONALLY-NOT CONSISTENT. PROVIDE THE INFORMATION ON THE DRAWING TO INDICATE WHAT THE "OCCASIONALLY" REFERENCES.
8. SHEET S.3; DETAIL 204: PROVIDE A DETAIL ON THE DRAWING INDICATING HOW THE C9 AND W10 ARE CONNECTED.
9. SHEET S.4; DETAIL 206: INDICATE NOTE 5 ON THE DETAIL.
10. SHEET A.1; BUILDINGS 1, 2, AND 3 FLOOR PLANS: FOR STORAGE RACKS OVER 6' IN HEIGHT UP TO 12', PROVIDE A DETAIL ON THE DRAWINGS FOR THE CONNECTION OF THE RACKS TO THE FLOOR.
11. SHEET A.1; BUILDING 1 FLOOR PLAN: CLEAR UP THE VERBIAGE AND DIMENSIONS IN OFFICE 05.
12. SHEET A.1; KEYNOTES: NOTES 15, 18, AND 22 WERE NOT LOCATED ON THE PLANS. VERIFY.
13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2013 SHANAE POWELL OUT TO CUSTOMER Completed
10/09/2013 CPIERCE1 REJECT SHELF Completed