| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/26/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/27/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 06/27/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 06/27/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the addition of the 3 sinks will not be overloading the existing water supply or waste piping. 2. Provide a waste and vent riser diagram. |
| 06/27/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/27/2006 | DAVE MANN | FIRE | REVIEW | Approved | |
| 06/30/2006 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/30/2006 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | Electrical review to continue O/C when Applicant presents occupancy information. Fault calculations 38789, 15521. Then check per NEC 518, 520. |
| 06/30/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/30/2006 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |