Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T06CM02997
Review Name: COMMERCIAL TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2006 | TERRY STEVENS | ZONING | REVIEW | Approved | |
05/19/2006 | ANY | WWM | REVIEW | Active | |
05/19/2006 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
05/22/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/22/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
05/22/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/22/2006 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/22/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the requirements of the new equipment; K14 is scheduled for water service but K15 is not (Sheet A1.0). All three are shown as being connected to water on sheet P1.0. 2. The proposed double-check valves are not approved for use with carbonators. Reference Section 603.4.13 and Table 6-2, UPC 2003. 3. Provide sufficient information to show that the existing 2" vent will not be handling over 24 fixture units. Reference Section 904.1 and Table 7-5, UPC 2003. |
05/22/2006 | MARTIN BROWN | FIRE | REVIEW | Approved |