Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T06CM02997
Parcel: 11712037A

Address:
17 W CONGRESS ST

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T06CM02997
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2006 TERRY STEVENS ZONING REVIEW Approved
05/19/2006 ANY WWM REVIEW Active
05/19/2006 SUZANNE BOHNET ENGINEERING REVIEW Approved
05/22/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/22/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/22/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
05/22/2006 ROBERT SHERRY WATER REVIEW Approved
05/22/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the requirements of the new equipment; K14 is scheduled for water service but K15 is not (Sheet A1.0). All three are shown as being connected to water on sheet P1.0.
2. The proposed double-check valves are not approved for use with carbonators. Reference Section 603.4.13 and Table 6-2, UPC 2003.
3. Provide sufficient information to show that the existing 2" vent will not be handling over 24 fixture units. Reference Section 904.1 and Table 7-5, UPC 2003.
05/22/2006 MARTIN BROWN FIRE REVIEW Approved