Permit Number: T06CM02975
Parcel: 119310120

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T06CM02975
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2008 ANDREW CONNOR NPPO REVIEW Denied Submit two copies of the approved Overlay Zone Plans (Case # T06SA00248) for reference. The application will be reviewed for compliance only when the approved documents are included in the submittal. Additional comments may apply upon subsequent reviews.
05/12/2008 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 5-14-08
Activity: T06CM02975
Address: 3007 W. Via De Suenos
Applicant: Rudy Garcia

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

MECHANICAL PLAN:
3. Gas appliances shall comply with the combustion air requirements in Chapter 17 of the 2006 IRC. Show compliance for all appliances. Confined spaces require a minimum of two 100 SQ. IN. openings, M1702.2.
4. Provide gas piping for structure or submit exemption documentation, Arizona Statute 30-809.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review
05/14/2008 HEATHER THRALL ZONING REVIEW Denied Please provide two copies of the approved Overlay Zone Plans (Case # T06SA00248). The sitep plan for the residence will be reviewed for compliance when the approved overlay documents are included in the submittal.

Please note that additional comments may apply upon the next review.

I have confirmed with the CDRC manager, Patricia Gehlen, that the overlay plan has not expired due to the extension that was given for the review of the actual house site plan.

I may be reached at Heather.Thrall@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
05/14/2008 SUE REEVES REJECT SHELF Completed