Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T06CM02086
Review Name: SITE
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/23/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/02/2007 | WILLDAN | ENGINEERING | REVIEW | Denied | |
05/14/2007 | SREEVES1 | ADA | REVIEW | Passed | |
05/14/2007 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
05/15/2007 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
05/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The minimum slope for a 6" building sewer is ¼" per foot. A minimum slope of 1/8" per foot may be used if it can be shown that it is impractical to obtain a slope of ¼" per foot. Reference Section 718.1, UPC 2003. 2. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 2003. |
05/30/2007 | WILDAN | ZONING | REVIEW | Approved | |
05/30/2007 | WILDAN | ZONING HC SITE | REVIEW | Approved |