Permit Number: T06CM02086
Parcel: 13413057F

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: SITE

Permit Number - T06CM02086
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2007 MARTIN BROWN FIRE REVIEW Approved
05/02/2007 WILLDAN ENGINEERING REVIEW Denied
05/14/2007 SREEVES1 ADA REVIEW Passed
05/14/2007 ANDREW CONNOR LANDSCAPE REVIEW Approved
05/15/2007 ANDREW CONNOR NPPO REVIEW Approved
05/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum slope for a 6" building sewer is ¼" per foot. A minimum slope of 1/8" per foot may be used if it can be shown that it is impractical to obtain a slope of ¼" per foot. Reference Section 718.1, UPC 2003.
2. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 2003.
05/30/2007 WILDAN ZONING REVIEW Approved
05/30/2007 WILDAN ZONING HC SITE REVIEW Approved