Permit Number: T06CM02086
Parcel: 13413057F

Address:
51 S PANTANO RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T06CM02086
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor review & 5th floor manhole tap permit. 6" HCS to 15" public sewer manhole.
04/23/2007 ROBERT SHERRY WATER REVIEW Approved
04/23/2007 MARTIN BROWN FIRE REVIEW Denied The double check on the fire line is not required.

Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.
05/02/2007 VFLORES1 ZONING REVIEW Approved
05/09/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact fee's do apply; East District; 11,600 Square Feet; $23,110.80
06/06/2007 LOREN MAKUS ENGINEERING REVIEW Approved The site plan must be approved before the building permit is approved.
06/06/2007 LOREN MAKUS ENGINEERING REVIEW Approved Site plan has been approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/11/2007 THAUSER1 OUT TO CUSTOMER Completed